Range of product; SMART-Pump
Product or component type; Variable speed drive
Product specific application; Pump, Chiller
Network number of phases; 3 phases
[Us] rated supply voltage;380... 440 V - 15...10 %
Supply frequency;50... 60 Hz
Motor power kW; 55 kW for normal duty;
Motor power hp; 75 hp for normal duty
Maximum transient current; 132 A during 1 min (normal duty),165 A during 1 s (normal duty),198 A during 0 s (normal duty)
Asynchronous motor control profile; Sensorless vector control (SVC)
Voltage/frequency ratio (V/f); Speed drive output frequency,0... 599 Hz
Continuous output current; 110 A
EMC filter; Class C3 EMC filter