smoke detector System

28.75

59.51-52%

Product description

OPTICAL SMOKE DETECTOR IS DESIGNED TO DETECT SMOKE AND SIGNAL A FIRE ALARM.

  • f the detector senses smoke, a relay is activated. Since FDR26 does not react to temperature changes, it is suitable for installation in data centers and telco rooms.
  • Optical smoke detection reacts to smoke that enters the detection chamber. Presence of smoke is indicated by turning on a LED and switching a relay. Smoke is detected only if it directly "hits" the sensor. The alarm ends when the detection chamber is free of smoke particles.

Power:10.5...14V DC

Start-up time: 60 s

Alarm indication: Red LED, switching a relay

Relay contact: up to 1A / 30V DC (0.5A / 125V AC)

Detection: Contains an optical detection chamber

Protected area: Max. 40 m2 (430 sq. ft), max. height 7 m (22 ft)

Distances: Max. distance between detectors 8 m (25 ft), max distance from a wall 4 m (13 ft)

Operating temperatures: 0°C to 70°C (32°F to 158°F)

Max. air velocity: 600 m/min

Measuring period:3 to 5 seconds

Test: Alarm can be activated by holding a magnet near the TEST point

Standard: Conforms to EN54-7

Operating environment: Indoor

Cover: IP 42 (EN 60 529) 