DSPPA DSP5311EN EN54-24 Surface Mount Ceiling Speaker, 12W
147.25ر.س
Product description
The DSPPA DSP5311EN is a surface mount ceiling speaker certified to EN54-24:2008, running on a 100V line with 12W, 6W and 3W taps. It is made for voice evacuation and public address inside towers, hospitals and commercial complexes.
====
The DSPPA DSP5311EN is a voice alarm speaker certified to EN54-24:2008. It mounts on the ceiling surface and runs on a 100V line at up to 12W. DSPPA built it for voice evacuation and public address inside buildings, where an evacuation message has to reach every person in a corridor or hall clearly.
DSPPA DSP5311EN specifications
From the official product page on DSPPA's site:
- Standard: EN54-24:2008, environmental class Type A for indoor use.
- Protection: IP21C to EN60529.
- Driver: 6.5-inch (Ø165mm) full-range, dual cone.
- Transformer: 100V with 12W, 6W and 3W taps; 24W music power.
- Sensitivity 89dB; maximum SPL 100dB at 1 meter.
- Response: 230Hz to 16kHz at -10dB.
- Size: 203mm diameter, 95mm deep; weight 1.02kg; white finish.
What EN54-24 certification means
EN54-24 is the loudspeaker part of the European EN54 series for fire detection and fire alarm systems. It sets performance and test requirements for voice alarm speakers. DSPPA publishes a Declaration of Performance for its fire-rated speakers on its website. If the consultant's material schedule calls for EN54-24 speakers, this model meets that line item.
Flame-retardant materials and thermal protection
The enclosure is ABS rated V0 and the grille is painted aluminum. The terminal block is ceramic and carries a thermal fuse that protects the speaker from overheating. Double cable ferrules are included, so the line can loop from one speaker to the next (daisy-chain) with tidy, easy-to-inspect wiring.
Coverage and speaker spacing
Coverage is 180° at 500Hz, 95.6° at 1kHz and 116° at 2kHz, narrowing to 48° at 4kHz and 35° at 8kHz. A sound designer feeds these figures into the layout software to set speaker spacing, so evacuation messages stay intelligible everywhere. The three taps let you balance each zone: 3W for small offices, 6W for corridors, 12W for open halls.
Where it sits in a PAVA system
A speaker alone is not an evacuation system. You also need a PAVA controller and amplifier that receive the fire alarm panel's signal and broadcast recorded messages to the right zones, such as the 8-zone DSPPA PAVA9500. DSP5311EN speakers connect to the amplifier's 100V outputs and are grouped by the building's evacuation plan: one zone per floor in a tower, or per wing in a hospital or hotel. On normal days the same system handles paging and background music.
Applications in Saudi Arabia
- Office towers and commercial complexes with exposed-ceiling corridors and halls.
- Hospitals and hotels running a PAVA system for daily paging and emergency messages.
- Warehouses and factories with concrete ceilings, indoor areas only given the IP21C rating.
- Universities and large schools.
DSP5311EN vs DSP5311 vs DSP2254EN
The standard DSP5311 shares the surface-mount design but is rated at 6W, runs on 70V or 100V, covers 140Hz to 16kHz and uses an engineering plastic body without EN54 certification. The DSP5311EN delivers 12W on 100V only and adds EN54-24 certification, a V0 body and a thermal fuse. DSPPA's other EN54 ceiling speakers include the DSP2254EN at 10W with a rear fire dome and the DSP602EN at 6W.
Frequently Asked Questions
Is the DSP5311EN EN54 certified?
Yes. DSPPA lists it as certified to EN54-24:2008, Type A for indoor use, and publishes the Declaration of Performance on its site.
Can the DSP5311EN run on a 70V line?
The official specification lists a 100V transformer only, with 12W, 6W and 3W taps, so it is designed for 100V systems.
Can I install it outdoors?
No. It is rated IP21C and Type A, which means indoor use only.
Specifications
- Model: DSP5311EN
- Standard: EN54-24:2008, loudspeaker for voice alarm systems in fire detection and fire alarm systems
- EN54-24 environmental class: Type A, indoor
- IP rating (EN60529): IP21C
- Speaker type: 1-way dual cone, full range Ø165mm
- Transformer: 100V (12W / 6W / 3W)
- Nominal / music power: 12W / 24W
- On-axis frequency response (-10dB): 230Hz to 16kHz
- Sensitivity (1m, 1W): 89 dB
- Max SPL (1m, Pmax): 100 dB
- Coverage angle (-6dB): 180° (500Hz), 95.6° (1kHz), 116° (2kHz), 48° (4kHz), 35° (8kHz)
- Directivity index DI: -3.8 (500Hz), 3.4 (1kHz), 5.1 (2kHz), 9.1 (4kHz), 10.8 (8kHz) dB
- Directivity factor Q: 0.4 (500Hz), 2.2 (1kHz), 3.2 (2kHz), 8.2 (4kHz), 12 (8kHz)
- Nominal impedance @ 1kHz: 833Ω (12W), 1.66kΩ (6W), 3.33kΩ (3W)
- Dimensions (Ø × depth): 203 × 95 mm
- Weight: 1.02 kg
- Material: ABS V0, painted aluminum grille
- Colour: White
- Connections: Ceramic connector with thermal fuse; double cable ferrules for daisy-chain wiring
Features
- EN54-24:2008 certified (Type A, indoor): matches material schedules that require EN54 speakers for voice evacuation.
- 12W, 6W and 3W taps on 100V: set the power per zone, from a small office to an open hall.
- ABS V0 enclosure with aluminum grille: flame-retardant materials, per DSPPA.
- Ceramic connector and thermal fuse: overheat protection for the speaker circuit.
- Surface mount, 203mm diameter, 95mm deep: fits exposed ceilings that cannot be cut.