DSPPA PAVA9425E 4-Zone 1000W Voice Alarm Expansion Amplifier

7793.70

Product description


The DSPPA PAVA9425E is an expansion unit for PAVA9500 systems that adds 4 zones on 1000W, backed by a standby amplifier of the same rating. It is built for large zones with many speakers, such as car parks, warehouses and exhibition halls.

====

The DSPPA PAVA9425E is a 4-zone expansion amplifier rated at 1000W on 100V lines, paired with a standby amplifier of the same size that cuts in automatically if the main one fails. It runs under a PAVA9500 host and can share the same system with PAVA9500E units. Its natural home is a zone that carries a lot of speakers: a large showroom, a car park level or a warehouse with long aisles.

Why choose the DSPPA PAVA9425E

More power on fewer zones: 1000W with 4 zones, while the 8-zone PAVA9500E is rated at 500W. If one zone holds dozens of speakers, this is the unit that can drive them.

  • 4 A/B speaker outputs with independent on/off and volume per zone.
  • Two 1000W digital amplifiers with automatic changeover and fault detection.
  • Up to 30 units per host, for up to 128 zones including the host's 8, according to DSPPA.
  • AC mains plus a DC 24V/34A battery input.

Connecting and configuring the unit

The unit links to the host through two RJ45 CAN bus ports, wired in a daisy chain or a loop. DIP switches 1 to 5 set the unit ID, and switch 6 enables the termination resistor on the last unit in the chain.

Local messages and clear priorities

A built-in alarm and message player holds up to 10 MP3 sources in 4MB of memory, swapped over Micro USB. Emergency audio from the host and fire alarm dry-contact triggers sit at the top of the priority list, followed by background music from the host and the external inputs. You can page one zone without stopping background music in the others.

Inputs, outputs and supervision

  • 2 balanced mic inputs, LINE1-2 balanced, LINE3-4 single-ended, and 1 line output.
  • 4 trigger inputs (dry contact or 3.3-24V level) and 4 programmable dry-contact outputs.
  • 4 24V override outputs at 0.2A each, forced on in emergency mode, 19W total maximum.
  • Open, short and ground fault detection on speaker lines, with a fault LED per zone.
  • System fault output, EVAC state output and fire reset input.

Where it fits in Saudi Arabia

  • Car parks in malls and towers: one zone covering an entire level with horn speakers.
  • Warehouses and factories in Dammam and Riyadh: long aisles and high ceilings that need more speakers.
  • Exhibition halls and large venues: few zones, each covering a wide floor area.

PAVA9425E or PAVA9500E?

The PAVA9425E gives you 4 zones and 1000W; the PAVA9500E gives you 8 zones and 500W. Both are 2U, both carry a standby amplifier and both run under the PAVA9500 host. A host accepts up to 30 PAVA9425E or 19 PAVA9500E units. The PAVA9425E needs a DC 24V/34A supply instead of 17A, its 24V outputs are limited to 19W instead of 38W, and it has 4 trigger inputs instead of 8.

Frequently Asked Questions

Does the PAVA9425E work on its own?

No. It is an expansion unit for the PAVA9500 host and can be mixed with PAVA9500E units in the same system.

How many PAVA9425E units can one host take?

Up to 30 units on a single PAVA9500 host, for a system of up to 128 zones according to DSPPA.

Specifications

  • Model: PAVA9425E
  • Type: 4-zone expansion amplifier with main/backup switching
  • Compatible host: PAVA9500 (can be combined with PAVA9500E)
  • Chassis: 2U, black oxidized aluminum alloy, frosted panel
  • Rated output power: ≥1000W (100V)
  • Amplifiers: 2 x 1000W digital amplifiers (main and backup), automatic changeover
  • Zones: 4 zones, A/B loop outputs 0-100V, independent on/off and 6-step volume
  • Input sensitivity: LINE: 1000±100mV, 10kΩ
  • Harmonic distortion: <1% @1kHz (MIC and LINE)
  • Frequency response: MIC: 80Hz-15kHz (±3dB); LINE: 50Hz-18kHz (±3dB)
  • S/N ratio: MIC: >75dB (A); LINE: >80dB (A)
  • AUX output: 1000mV, 80Hz-15kHz (±3dB), <1% @1kHz
  • Audio I/O: MIC1-2 balanced, LINE1-2 balanced, LINE3-4 single-ended, LINE OUT
  • Local message player: 4MB MP3 storage, up to 10 sources, updated via Micro USB
  • Control I/O: 4 dry-contact or level (3.3-24V) inputs, 4 programmable dry-contact outputs
  • 24V outputs: 4 outputs, 0.2A each, forced on in emergency mode, 19W total maximum
  • System contacts: System fault output, EVAC state output, fire reset input (t≥0.5s)
  • Host link: 2 x RJ45 CAN bus, cascade or loop
  • Addressing: DIP 1-5 for ID, DIP 6 for bus termination
  • Maximum per host: 30 units (128 zones including host)
  • Line supervision: Open, short and ground fault detection
  • Power supply: AC 50-60Hz; DC 24V/34A, automatic changeover
  • Fuse and rated input: F10AL 250V; 1500VA
  • Unit dimensions (LxWxH): 483 x 430 x 88 mm

Features

  • 1000W with 4 zones: high power for large zones with many speakers.
  • Two 1000W amplifiers, duty and standby: automatic changeover on a fault, with amplifier fault detection.
  • Up to 30 units per PAVA9500 host: a system of up to 128 zones, and it can be mixed with PAVA9500E units.
  • 4 trigger inputs, 4 dry-contact outputs and 4 24V outputs: direct ties to the fire panel and volume overrides.
  • 4MB message player: up to 10 MP3 sources stored in the unit, updated over Micro USB.

Questions you might have

‌
‌
‌‌
‌
‌
‌‌
‌
‌
‌‌
‌
‌
‌‌
‌
‌
‌‌
‌
‌
‌‌
‌