Fire alarm control panel 2 zones Zeta

1249

Out of Stock

Product description

Infinity 8 control panel in ABS enclosure with the most attractive and modern design and fire resistance, using a switching power supply. It features a fully removable front cover, improving ease of access to cable connections. The Infinity 8 panel can also be ordered with a metal back box for easy installation of batteries up to 7ah inside the panel structure. To order this version, add "/M" to the end of the model number (e.g., IN1/M, IN2/M, etc.). Features: - Password access - Eliminates the problem of missing keys - Single man test facility - Area and sound device disablement facility - Space for up to 3Ah batteries - Safer delay option - 4 safer circuits (IN4, IN6, and IN8) - Safer circuits 3 and/or 4 can be configured as Aux 24V input - Supplies meet all requirements of the latest EN54 Part 2 and Part 4 Model IN2 Part number 37-650 Power supply voltage 230V AC +10% / -15% at 50/60Hz System voltage 24V DC (nominal) Area voltage 21V DC (nominal) Alarm output Safer 2 × 150mA @ 24V DC 4 × 150mA @ 24V DC Fault relay 1 × free voltage relay, SELV @ 1A max Nine zones 32 devices per zone Remote sounder operation via N/O contact connected to change category Sounder activation delay from 0 to 10 minutes in 1-minute increments End-of-line zone diode 1N4002 (cathode strip to zone +ve) End-of-line resistor 10K Charger voltage 27.6V Battery cut-off voltage below 20V Internal resistance of the battery 0.9 ohms Enclosure size 371 × 302 × 93 mm Weight 3 kg (excluding batteries) Maximum battery space 2 × 3.4Ah, 12V sealed lead-acid batteries